Reducing Clearances to Combustibles: How to Read Table M1306.2 (IRC 2024)
How to use IRC 2024 Table M1306.2 to reduce appliance and vent connector clearances with protection: picking the column group, Column 1 vs 2, and the airspace rules.
Code references covered
IRC 2024 Section M1306.1 · IRC 2024 Section M1306.2.1 · IRC 2024 Section M1306.2.2 · IRC 2024 Section M1306.2.3
Appliances and vent connectors must keep their listed distance from combustible materials (IRC 2024 Section M1306.1). When there is not enough room, the code lets you shrink that distance by protecting the combustible surface — either with a listed, labeled protective assembly (Section M1306.2.1) or with one of the forms of protection in Table M1306.2 (Section M1306.2.2). The table is a favorite on the M1 because it rewards careful reading.
Move 1 — Start from the unprotected clearance
The table is organized by the clearance that would be required without protection: 36, 18, 12, 9 or 6 inches. That number comes from the appliance label, the manufacturer's instructions or another code section. Pick the matching column group first.
Move 2 — Column 1 or Column 2
Each group has two columns. Column 1 is for clearances above an appliance or a horizontal connector. Column 2 is for the sides and rear of an appliance, vertical connectors and single-wall metal pipe. Heat rises, so the allowed reduction above is smaller — that is why Column 1 values are larger, and why some forms of protection (masonry walls) have no Column 1 value at all.
Move 3 — Find the row for the protection
Rows list the type of protection: masonry walls with or without a ventilated airspace, insulation board, and No. 24 gage galvanized sheet steel in several combinations. Match the description exactly — “with a ventilated airspace” and “without” are different rows with different answers.
The airspace rules that come with it
Section M1306.2.2 adds requirements for protection that uses a ventilated airspace, and the table notes add more. The ones examiners ask about:
- At least 1 inch of airspace between the protection and the combustible wall.
- Edges of the protection left open at least 1 inch so air can circulate.
- At least 1 inch between the appliance and the protector.
- Spacers and ties must be noncombustible and not placed directly opposite the appliance or connector.
- The protection must cover the combustible surface far enough in every direction (see Figure M1306.1).
The solid-fuel limit
Section M1306.2.3 restricts the table for solid-fuel appliances: it cannot be used at all when the listed clearance is 12 inches or less, and it can never take a larger listed clearance below 12 inches. Expect at least one question that hinges on this.
Practice
Our calculation workshop has clearance-reduction problems that make you pick the group, the column and the row, then explains each step — the same three moves you will use on the exam.
For the exact code language, read the sections on the official ICC Digital Codes site. We cite section identifiers and explain the logic in our own words — always confirm the current text and any local amendments there.
Practice this topic with IRC 2024-based questions
See how our practice questions and explanations reinforce what you just read. No credit card required to try the demo.
Related guides
Appliance Installation and Clearances (IRC 2024)
Access, working space, clearances, ignition-source elevation, and condensate basics.
Chimneys and Vents: How to Read the IRC 2024 Rules
Vent types, terminations, and connectors — and how the chimney/vent sections are organized.
Common M1 Pitfalls: Mistakes to Avoid on the Mechanical Exam
Mixing up chapters, misreading tables, and time traps — plus a fix for each.
Frequently asked questions
- Can Table M1306.2 be used for a wood stove?
- Only in part. Section M1306.2.3 prohibits using the table for solid-fuel appliances listed for clearances of 12 inches or less, and for appliances listed for more than 12 inches it cannot reduce the clearance below 12 inches.
- When do I use Column 1 versus Column 2?
- Column 1 applies to clearances above an appliance or a horizontal connector. Column 2 applies to the sides and rear of an appliance, vertical connectors and single-wall metal pipe.