Combustion Air Calculations: Worked Examples (IRC 2024)

Step-by-step combustion air examples for the ICC M1: indoor volume, openings between rooms, two outdoor openings, louvers and the one-opening method under IRC 2024.

Code references covered

IRC 2024 Section G2407.5.1 · IRC 2024 Section G2407.5.3 · IRC 2024 Section G2407.6.1 · IRC 2024 Section G2407.6.2 · IRC 2024 Section G2407.10

Combustion air questions on the M1 are almost always a short calculation: add up the appliance input, apply one ratio from the code, and compare the result with what the house provides. The hard part is picking the right ratio. This guide walks through five typical situations in the order you would check them on a real job. For the rules behind them, see our combustion air requirements guide.

Step zero: total the input

Every method starts from the total input rating of all appliances in the space, not the largest appliance. A 90,000 Btu/h furnace and a 40,000 Btu/h water heater in the same room means you work with 130,000 Btu/h. Forgetting the water heater is the most common way to miss these questions.

Example 1 — Is the room big enough on its own?

Under the standard method in IRC 2024 Section G2407.5.1, the space needs 50 cubic feet for every 1,000 Btu/h. For 130,000 Btu/h: 130 × 50 = 6,500 cubic feet. A 17 × 12 ft room with a 9 ft ceiling holds 1,836 cubic feet, so indoor air from that room alone is not enough. A full basement of 30 × 28 × 8 = 6,720 cubic feet would be. One caveat the exam likes: if the house is known to be tighter than 0.40 air changes per hour, Section G2407.5 sends you to the known air infiltration rate method instead.

Example 2 — Borrowing air from the next room

When the appliance room is too small, you can count an adjoining room as part of the volume if the two are connected by properly sized openings (Section G2407.5.3). On the same story, each of two openings needs 1 square inch per 1,000 Btu/h of total input, but never less than 100 square inches. One opening starts within 12 inches of the top and one within 12 inches of the bottom, and no dimension may be less than 3 inches.

  • 130,000 Btu/h → 130 square inches for each opening.
  • 70,000 Btu/h → 70 square inches by the ratio, so the 100 square inch minimum governs.

Between stories (for example a basement and the floor above) the rule changes to a total of 2 square inches per 1,000 Btu/h, so 130,000 Btu/h needs 260 square inches of openings in total.

Example 3 — Two openings to the outdoors

If indoor air will not work, bring it from outside. With the two-permanent-openings method in Section G2407.6.1, the ratio depends on how the air arrives:

  • Directly through an exterior wall or through vertical ducts: 1 square inch per 4,000 Btu/h for each opening.
  • Through horizontal ducts: 1 square inch per 2,000 Btu/h for each opening.

For 130,000 Btu/h through vertical ducts: 130,000 ÷ 4,000 = 32.5 square inches per opening. The same appliances fed through horizontal ducts need 65 square inches per opening — twice as much, because horizontal runs move air less effectively.

Example 4 — Louvers of unknown free area

Those areas are free (net) areas. When the opening is covered by a louver or grille whose free area is not known, Section G2407.10 tells you to assume 25 percent for wood and 75 percent for metal. To deliver 32.5 square inches through a wood louver you need 32.5 ÷ 0.25 = 130 square inches of louver; with metal, 32.5 ÷ 0.75 ≈ 43.3 square inches.

Example 5 — A single opening

The one-permanent-opening method in Section G2407.6.2 uses one opening near the top of the enclosure (within 12 inches), with at least 1 inch of clearance at the sides and back of the appliance and 6 inches at the front. The opening needs 1 square inch per 3,000 Btu/h and must be at least as large as the combined area of all vent connectors in the space. With 130,000 Btu/h, a 5-inch and a 4-inch round connector:

  • By input: 130,000 ÷ 3,000 ≈ 43.3 square inches.
  • By connectors: π × 2.5² + π × 2² ≈ 19.6 + 12.6 = 32.2 square inches.
  • The larger value governs: about 43.3 square inches.

Practice with fresh numbers

The fastest way to make these ratios automatic is repetition with new numbers each time. Our calculation workshop generates unlimited combustion air problems like the ones above and shows the full solution after you answer.

For the exact code language, read the sections on the official ICC Digital Codes site. We cite section identifiers and explain the logic in our own words — always confirm the current text and any local amendments there.

Practice this topic with IRC 2024-based questions

See how our practice questions and explanations reinforce what you just read. No credit card required to try the demo.

Related guides

Frequently asked questions

How much indoor air does a gas appliance need under the standard method?
The standard method in IRC 2024 Section G2407.5.1 requires 50 cubic feet of room volume for every 1,000 Btu/h of total appliance input in the space. A 100,000 Btu/h furnace plus a 40,000 Btu/h water heater therefore needs 7,000 cubic feet.
What if the louver free area is unknown?
Section G2407.10 tells you to assume 25 percent free area for wood louvers and 75 percent for metal louvers and grilles. Divide the required free area by that fraction to get the gross louver size.