How to Size Gas Piping with the Longest Length Method (IRC 2024)
Learn the IRC 2024 longest length method for sizing gas piping: total the load, find the most remote outlet, pick one table row, and size every section from it.
Code references covered
IRC 2024 Section G2413.2 · IRC 2024 Section G2413.4 · IRC 2024 Section G2413.4.1 · IRC 2024 Appendix CA
Gas pipe sizing looks intimidating because the capacity tables are dense, but the M1 almost always tests the same procedure: the longest length method. Once you have the steps in order, each question takes about a minute. This guide explains the method; keep your code book open to the sizing table for your material while you read.
Step 1 — Know which table you are in
IRC 2024 Section G2413.4 points to a family of capacity tables, one for each material and set of conditions. Each table states its gas type, inlet pressure, allowable pressure drop and specific gravity in the header. Confirm those match the question before you read a single number — choosing the wrong table is a classic trap.
Step 2 — Add up the load
Section G2413.2 sizes piping for the sum of the maximum input of all appliances served, assuming they all run at once. The low-pressure tables are in cubic feet per hour, so convert Btu/h by dividing by the heating value of the gas. Exam questions usually give 1,000 Btu per cubic foot; in practice the value comes from the gas supplier (Appendix CA explains this conversion).
Step 3 — Find the longest length
Under Section G2413.4.1, measure from the point of delivery (usually the meter) to the most remote outlet. That single length is used for every section of the system — even a short branch near the meter. If the length is not listed in the table, use the next longer row; never round down.
Step 4 — Size each section for its own load
Stay in that one row. For each section, total only the appliances downstream of it, then move across the row to the first capacity that is equal to or greater than that load. The column heading is the size.
Worked example
A meter feeds section A to a tee. From the tee, section B continues to a furnace (100,000 Btu/h) and section C branches to a water heater (40,000 Btu/h). A is 15 ft, B is 25 ft and C is 10 ft.
- Loads: furnace 100 CFH, water heater 40 CFH; section A carries both, 140 CFH.
- Longest length: meter → furnace = 15 + 25 = 40 ft (meter → water heater is only 25 ft).
- Use the 40 ft row for all three sections.
- Size A for 140 CFH, B for 100 CFH and C for 40 CFH from that row.
Notice that section C is sized with the 40 ft row even though it is only 25 ft from the meter. That conservatism is the whole point of the method. (The branch length method in Section G2413.4.2 refines this for branches, but the exam usually asks for the longest length method unless it says otherwise.)
Common mistakes
- Sizing each section with its own length instead of the longest length.
- Using the load of one appliance for a section that feeds several.
- Rounding the length down to a shorter row.
- Reading a table with the wrong pressure drop or material.
Practice
Our calculation workshop builds new single-run and branched-system sizing problems every time, using the Schedule 40 table, and walks through the answer step by step.
For the exact code language, read the sections on the official ICC Digital Codes site. We cite section identifiers and explain the logic in our own words — always confirm the current text and any local amendments there.
Practice this topic with IRC 2024-based questions
See how our practice questions and explanations reinforce what you just read. No credit card required to try the demo.
Related guides
Fuel Gas Supply Basics for the M1 Exam (IRC 2024 Chapter 24)
Piping materials, sizing, shutoff valves, and testing — a map of Chapter 24 fuel gas.
Combustion Air Calculations: Worked Examples (IRC 2024)
Five worked examples: room volume, openings, outdoor air, louvers and the single-opening method.
How to Find a Code Section Fast During the Open-Book M1 Exam
A repeatable keyword → index → chapter → section → table workflow for open-book speed.
Frequently asked questions
- Which length do I use for each section of gas pipe?
- With the longest length method (IRC 2024 Section G2413.4.1) you use one length for every section: the length from the point of delivery to the most remote outlet. Each section is then sized for the load it carries using that single table row.
- What if my length falls between two rows of the table?
- Use the next longer length listed. The informative Appendix CA describes this step: select the row with the measured length or the next longer length if the exact length is not shown.