Water Supply Fixture Units, Demand, and Manifold Sizing (IRC 2024)

Worked example: total w.s.f.u. with IRC 2024 Table P2903.7, convert to gpm with Table P2903.7(1), then size a plastic or metallic manifold with Table P2903.9.1.

Code references covered

IRC 2024 Section P2903.7 · IRC 2024 Table P2903.7 · IRC 2024 Table P2903.7(1) · IRC 2024 Section P2903.9.1 · IRC 2024 Table P2903.9.1 · IRC 2024 Section P2903.9.2 · IRC 2024 Table P2903.1 · IRC 2024 Sections P2903.3, P2903.3.2, P2903.8

Checked against the 2024 IRC (Second Printing) on 2026-11-06. Confirm the edition your exam and jurisdiction use, and any local amendments.

Water Supply and Distribution is 22% of the P1, and pressure-and-volume questions are a steady part of it. The supply side has its own unit — the water supply fixture unit (w.s.f.u.) — and its own tables. This guide follows one house from fixtures to manifold size so you can see the whole chain.

The three-table chain

  1. Table P2903.7 gives w.s.f.u. values for fixtures and fixture groups. Section P2903.7 says the load is the total on the pipe being sized, and that a fixture not listed takes the value of a fixture with similar flow characteristics.
  2. Table P2903.7(1) converts the w.s.f.u. total into demand in gallons per minute.
  3. Table P2903.9.1 gives the maximum gpm for plastic and metallic manifolds by size. Per Section P2903.9.1, the total gpm is the demand for all outlets.

Hot, cold or combined

Table P2903.7 has three columns: hot, cold and combined. Use the combined value for a pipe that carries the total load, such as the water service or a cold manifold feeding everything. Use the hot or cold column for a pipe that carries only that side. A full-bath group, for example, is 1.5 hot, 2.7 cold and 3.6 combined.

Step 1: Total the fixture units

Worked example — A two-and-a-half-bath house

The house has two full baths, one half bath, a kitchen, a laundry and two hose bibbs.

Fixture or groupCombined w.s.f.u.CountSubtotal
Full-bath group with bathtub3.627.2
Half-bath group2.612.6
Kitchen group2.512.5
Laundry group2.512.5
Hose bibb2.525.0
Total19.8

The total is 19.8 w.s.f.u. Table P2903.7(1) lists whole-number loads, so we take the next listed load at or above the total, 20 w.s.f.u. — the conservative choice.

The hose bibb value has a note: 2.5 w.s.f.u. assumes a 2.5 gpm demand. If a hose bibb must supply more, take an equivalent value from Table P2903.7 or P2903.7(1).

Step 2: Convert to gallons per minute

Table P2903.7(1) has two halves: supply systems predominantly for flush tanks and those predominantly for flushometer valves. Homes with tank-type water closets use the flush-tank side. For our house, 20 w.s.f.u. converts to 19.6 gpm.

The flushometer column gives 35.0 gpm for the same 20 w.s.f.u. — nearly double. Reading the wrong half of this table is one of the easiest ways to lose a point. Other flush-tank values worth recognizing: 10 w.s.f.u. is 14.6 gpm, 15 is 17.5 gpm and 30 is 23.3 gpm.

Step 3: Size the manifold

Table P2903.9.1 lists maximum flow by nominal size:

Nominal sizePlastic, max gpmMetallic, max gpm
3/4 in.1711
1 in.2920
1 1/4 in.4631
1 1/2 in.6644

Worked example, continued

Demand is 19.6 gpm. A 3/4-inch plastic manifold carries 17 gpm — too small. A 1-inch plastic manifold carries 29 gpm and works. In metal, 1 inch carries 20 gpm, which also covers 19.6 gpm, but with almost no margin.

Why is metal rated lower? Note b of the table explains it: the limits are based on velocity, 12 feet per second for plastic and 8 feet per second for metal.

Second example — A smaller house

One full bath (3.6), a kitchen group (2.5) and a laundry group (2.5) total 8.6 w.s.f.u. Using the next listed load, 9 w.s.f.u. converts to 13.7 gpm on the flush-tank side. A 3/4-inch plastic manifold (17 gpm) is enough; a 3/4-inch metallic manifold (11 gpm) is not, so metal would need to be 1 inch.

Hot and cold manifolds: sizing each side

Many manifold systems use a separate hot manifold and cold manifold. Each one carries only its own side of the load, so each is sized from its own column of Table P2903.7. This is where the hot and cold columns earn their place.

Third example — Separate hot and cold manifolds

The house has two full baths, a kitchen group, a laundry group and one hose bibb.

Fixture or groupHotColdCombined
Full-bath group with bathtub × 23.05.47.2
Kitchen group1.91.02.5
Laundry group1.81.82.5
Hose bibb—2.52.5
Total w.s.f.u.6.710.714.7

Hot manifold: 6.7 rounds up to 7 w.s.f.u., which is 11.8 gpm on the flush-tank side. A 3/4-inch plastic manifold (17 gpm) works. A 3/4-inch metallic manifold (11 gpm) falls just short, so metal goes to 1 inch.

Cold manifold: 10.7 rounds up to 11 w.s.f.u., or 15.4 gpm. Again 3/4-inch plastic works and metal needs 1 inch.

Whole-house load: 14.7 rounds up to 15 w.s.f.u., or 17.5 gpm. That is just over the 17 gpm limit for 3/4-inch plastic, so a pipe carrying the whole house — such as a cold manifold that also feeds the water heater — would need to be 1-inch plastic.

Notice two things. First, the combined total (14.7) is less than hot plus cold (6.7 + 10.7 = 17.4): the table assigns each fixture its own combined value, so a combined pipe is always totaled from the combined column, never by adding the other two. Second, you add fixture units and convert once; you never add gallons per minute from separate conversions. Adding 11.8 and 15.4 would give 27.2 gpm, far above the 17.5 gpm the table actually gives for the combined load.

Other manifold rules to know

  • Section P2903.9 covers parallel manifolds for hot and cold water and gridded systems for cold water. Gridded hot water distribution is prohibited.
  • Section P2903.9.2: where the distribution line is 60 feet or less in developed length and the pressure at the meter is at least 40 psi, individual lines may be as small as 3/8 inch. Where a water heater is fed from the end of a cold water manifold, the manifold must be one size larger than the water heater feed.
  • Section P2903.9.4: fixture valves go at the fixture or at the manifold, and valves at the manifold must be labeled for the fixture served.

Where candidates slip

  • Mixing drainage fixture units (Table P3004.1) with water supply fixture units (Table P2903.7). They are different scales for different systems.
  • Using the hot or cold column for a pipe that carries the combined load.
  • Reading the flushometer half of Table P2903.7(1) for a house with tank-type water closets.
  • Checking a metallic manifold against the plastic column of Table P2903.9.1.
  • Rounding a fractional total down instead of up to the next load listed in Table P2903.7(1).
  • Converting hot and cold totals separately and adding the gallons per minute to get a combined demand.
  • Forgetting the end-fed water heater rule in P2903.9.2 when the cold manifold also supplies the heater.

Pressure limits around the system

Sizing assumes the water arrives with enough pressure. Section P2903.1 says the system is designed for peak demand using Table P2903.1, which lists a required flow rate and flow pressure at each outlet. For example, a lavatory needs 0.8 gpm at 8 psi, while a shower with a balanced-pressure or thermostatic mixing valve needs 2.5 gpm at 20 psi.

Where the public main or an individual water supply cannot deliver those minimums, Section P2903.3 requires the pressure to be raised with an elevated water tank, a hydropneumatic booster system or a booster pump. At the other end, static pressure may not exceed 80 psi; where the main is higher, an approved pressure-reducing valve goes at the connection to the water service pipe (Section P2903.3.2).

The water service pipe must be at least 3/4 inch (Section P2903.8). Beyond that minimum, the same section sizes service mains, branch mains and risers from demand, available pressure and friction loss through the meter and the developed length of pipe, using an accepted engineering method such as Appendix AP. Thermal expansion control is covered in the water heater guide.

For the exact code language, read the sections on the official ICC Digital Codes site. We cite section identifiers and explain the logic in our own words — always confirm the current text and any local amendments there.

Practice this topic with 2024 IRC-based P1 questions

Create a free account to practice P1 questions with written explanations and 2024 IRC references.

Related guides

Frequently asked questions

Which column of Table P2903.7(1) applies to a typical house?
Homes with tank-type water closets use the column for supply systems predominantly for flush tanks. The flushometer-valve column gives much higher demand for the same load, so reading the wrong column is a common error.
Why does a metallic manifold carry less flow than a plastic one of the same size?
Table P2903.9.1 is based on velocity limits: 12 feet per second for plastic and 8 feet per second for metal (note b), so the same nominal size is rated for less gpm in metal.
Can I add hot and cold demand in gpm to size a pipe that carries both?
No. Total the combined column of Table P2903.7 and convert that total once with Table P2903.7(1). Converting hot and cold separately and adding the gallons per minute overstates the demand.