Wall Framing Basics: Stud Size and Spacing, Top Plates, Notching and Boring (IRC 2024)

A B1 guide to IRC 2024 Table R602.3(5) stud size, height and spacing, R602.3.2 top plates, R602.6 notching and boring limits, and the basics of braced wall panels.

Code references covered

IRC 2024 Section R602.2 · IRC 2024 Section R602.3.1 · IRC 2024 Table R602.3(5) · IRC 2024 Sections R602.3.2, R602.3.3, R602.3.4 · IRC 2024 Section R602.6 · IRC 2024 Section R602.6.1 · IRC 2024 Sections R602.10, R602.10.2.2

Checked against the 2024 IRC (Second Printing) on 2026-11-14. Confirm the edition your exam and jurisdiction use, and any local amendments.

Wall Construction and Coverings is the largest B1 content area, and wood wall framing sits at the center of it. This guide covers the stud table, top plates, how much of a stud or plate can be cut for pipes and wires, and the basic vocabulary of wall bracing — all in IRC 2024 Section R602.

Stud grade first

Section R602.2 sets the minimum stud grade at No. 3, standard or stud grade. Utility grade is allowed only in limited cases, and Section R602.3.1 exception 1 caps those studs at 16 inches on center, supporting no more than a roof and ceiling, and 8 feet tall in exterior and bearing walls (10 feet in interior nonbearing walls).

Reading Table R602.3(5)

Table R602.3(5) gives the stud size, laterally unsupported height and maximum spacing. It has two halves:

  • Bearing walls — a height column, then four spacing columns by what the wall carries: a roof-ceiling assembly (or habitable attic) only; one floor plus a roof-ceiling; two floors plus a roof-ceiling; and one floor only.
  • Nonbearing walls — a height column and one spacing column.

A dash means that stud size is not allowed for that condition. The notes matter too: bearing walls must be sheathed on at least one side or have bridging at not more than 4 feet (note a), 2 × 3 studs may not be used in exterior walls (note b), and a habitable attic over 2 × 4 studs is limited to a 32-foot roof span (note c).

Worked example 1 — one floor plus a roof on 2 × 4s

The first-floor walls of a two-story house carry the second floor and the roof. For 2 × 4 studs, Table R602.3(5) allows a maximum spacing of 16 inches for one floor plus a roof-ceiling assembly. Studs at 24 inches on center fail. The framer can go to 16-inch spacing, or switch to 2 × 6 studs, which the table allows at 24 inches for the same load.

Worked example 2 — two floors plus a roof

The bottom story of a three-story house carries two floors and a roof. The 2 × 4 entry in that column is a dash, so 2 × 4 studs are not permitted. A 2 × 6 or 3 × 4 stud is allowed at 16 inches on center.

Worked example 3 — heights

Each stud size the table allows in bearing walls (2 × 4 through 2 × 6) shows a 10-foot laterally unsupported height. Taller bearing walls need exception 2 of Section R602.3.1 or an engineered design. A nonbearing 2 × 4 partition, by contrast, may be 14 feet tall at 24 inches on center.

Top plates and bearing

  • Section R602.3.2 — walls get a double top plate that overlaps at corners and at intersections with bearing partitions. End joints in the two plates must be offset at least 24 inches. Plates are at least 2-inch nominal and as wide as the studs. A single top plate is an exception with its own tie requirements in Table R602.3.2.
  • Section R602.3.3 — when joists, trusses or rafters are spaced more than 16 inches on center over bearing studs at 24 inches, each member must bear within 5 inches of a stud, unless one of the listed exceptions (heavier or tripled plates, or solid blocking) applies.
  • Section R602.3.4 — studs need full bearing on a 2-by (or larger) bottom plate at least as wide as the stud.

Notching and boring studs: the 25 / 40 / 60 rule

Section R602.6 limits how much of a stud can be cut. The limits are percentages of the stud depth, so run the numbers with actual dressed lumber sizes — 3 1/2 inches for a 2 × 4 and 5 1/2 inches for a 2 × 6.

CutLimit2 × 4 (3 1/2 in.)2 × 6 (5 1/2 in.)
Notch, exterior or bearing wall25% of depth7/8 in.1 3/8 in.
Notch, nonbearing partition40% of depth1.4 in.2.2 in.
Bored hole, any wall60% of depth2.1 in.3.3 in.
Bored hole that triggers doubling (exterior or bearing)over 40%over 1.4 in.over 2.2 in.

Two more conditions apply to every bored hole: its edge must stay at least 5/8 inch from the edge of the stud, and it may not be in the same section of the stud as a notch. Where a hole over 40% is bored in an exterior wall or bearing partition, the stud must be doubled, and no more than two successive doubled studs may be bored that way. Approved stud shoes are an alternative.

Worked example 4 — a 2-inch hole in an exterior 2 × 4

A plumber bores a centered 2-inch hole through a 2 × 4 stud in an exterior wall. 2 ÷ 3 1/2 ≈ 57%, which is under the 60% cap, and the remaining 3/4 inch on each side clears the 5/8-inch edge distance. But 57% is over 40% in an exterior wall, so the stud must be doubled — and the next two studs in a row cannot all be treated the same way.

Cutting top plates

Section R602.6.1 covers top plates in exterior and interior bearing walls. When piping or ductwork cuts, drills or notches more than 50% of the plate width, a galvanized metal tie at least 16 gage and 1 1/2 inches wide must be fastened across the opening with eight 10d nails on each side and must extend at least 6 inches past the opening. The tie is not required where the entire side of the wall with the cut is covered by wood structural panel sheathing.

Wall bracing basics

Wall bracing resists racking from wind and earthquakes. Section R602.10 is long, but inspection questions mostly use a few ideas:

  • Braced wall lines are straight lines in the floor plan where bracing is required (Section R602.10.1).
  • Braced wall panels are the sheathed or otherwise braced segments along those lines. The allowed bracing methods are in Table R602.10.4 and minimum panel lengths in Table R602.10.5.
  • Location — under Section R602.10.2.2, the nearest edge of a braced wall panel must be within 10 feet of each end of the braced wall line, and adjacent panel edges may be no more than 20 feet apart. Seismic Design Categories D0–D2 have their own rule.
  • Simplified bracing — Section R602.12 is an alternative path for buildings that meet its limits.

For the loads these walls carry from above, see floor joist and rafter span tables; for what is under them, see footing sizes.

For the exact code language, read the sections on the official ICC Digital Codes site. We cite section identifiers and explain the logic in our own words — always confirm the current text and any local amendments there.

Want to practice this topic under exam conditions?

B1 practice questions built on the 2024 IRC are in development. Join the waitlist and we'll email you when they open.

Free. We'll email you when B1 practice opens.

Also preparing for another exam? Try 10 free M1 questions · Try 10 free P1 questions

Related guides

Frequently asked questions

How deep can I notch a stud in a bearing wall?
Section R602.6 limits a notch in a stud in an exterior wall or bearing partition to 25 percent of the stud depth. Studs in nonbearing partitions may be notched up to 40 percent.
How large a hole can be bored in a stud?
A bored hole may be up to 60 percent of the stud depth with its edge at least 5/8 inch from the stud edge. In exterior walls and bearing partitions, a hole over 40 percent requires the stud to be doubled, and no more than two successive doubled studs may be bored that way.
How far apart must top plate splices be?
Section R602.3.2 requires end joints in a double top plate to be offset at least 24 inches.